Fire Extinguishing Systems - FS E103 LCD

FS E103 LCD
  • EXTINGUISHING PANEL 

  • Functional features

  • Conventional fire extinguishing control panel certificated by EN12094-1 and EN54-2/4 standards. The panel is designed for usingtogether with systems for gas, powder, aerosol, water and other types of active extinguishing.

  • FS 103E has 3 zones – 2 for activation of automatic fire detectors and 1 conventional fire zone. Automatic and manual operation modes (selectable via 3 positional key lock) allow the operators to choose the extinguishing process control.

  • The FS E103 panel is designed for extinguishing in one zone and can operate with solenoids, pressostats and other kind of actuators.

  • The panel has a built-in display where over 30 functions can be programmed. This allows the functions to be adapted to each firefighting object.

  • There is a built-in real-time clock and an archive of up to 1,600 events.

  • Inputs Specifications:

  • •    L1 and L2– Conventional Zones for extinguishing

  • •    L3 Conventional Zone for Fire Alarm

  • •    Low Press. input – supervised balanced input

  • •    Manual release input – supervised balanced input

  • •    Mode select input – supervised balanced input for switching between Manual and Automatic operation mode

  • •    Hold input – supervised balanced input

  • •    On/Off Exting – supervised balanced input

  • Outputs Specifications:

  • •    S 1 (Sounder 1) – Monitored, 24VDC, 500mA

  • •    S 2 (Sounder 2) – Monitored, 24VDC, 500mA

  • •    Rel 1ST Stage 1 relay “Fire Alarm” (NC, COM, NO), 5-30VDC/1A

  • •    Rel 2ST Stage 2 relay “Extinguishing Activated” (NC, COM, NO), 5-30VDC/1A

  • •    Fault relay(NC, COM, NO), 5-30VDC/1A

  • •    Extinguish output (EN 12094-1), Monitored, 24VDC/1A 15min, 24VDC/3A 100ms

  • •    OC1 – in case of Extinguish disable – open collector type

  • •    OC2 – in case of Manual mode activeextinguish disable – open collector type

  • •    OC3 – in case of Low pressure – open collector type

  • •    OC4 – in case of Hold Activation  – open collector type

  • Programming of system times

  • EXTINGUISHING DURATION TIME – from 5 sec. to 15 min.

  • EXTINGUISHING DELAY TIME – from 0 to 60 seconds

  • RESET HOLD TIME – from 0 to 30 min.